Ekhwesi's three phase integrated BEC32 range, with BS footprint, are ideal meters for the retrofit market, whether residential, commercial or light industrial.
The meters are exceptionally hardy and robust, making them ideal for a wide variety of installation environments. An added feature of the range is the ability to detect tampering, even in the absence of an incoming supply.
Description | Value |
---|---|
Voltage ratings
|
220VAC - 230VAC 50Hz |
Current ratings
|
10A100A40mA50mA (Earth leakage only)UC2 |
Nominal power consumption |
1.6W / 9VA |
Accuracy |
Class 1 (maintained throughout life cycle of product) |
Over voltage rating |
420VAC for 48 hours |
Short circuit rating |
Short-circuit withstand 3.0kA |
Protection |
Power overload Current overload Thermal overload Over / under voltage Phase imbalance Meter tampering |
Environmental
|
-10°C to +55°C -25°C to +70°C 95% non-condensing PL - IP54 30V/m |
Status indicators |
Rate LED (1000 pulses / kWh) |
Installation
|
BS7856 - AsymmetricalDouble insulation |
Terminals
|
Live:Cage clamp 25mm Neutral:Cage clamp 25mm |
Interrogation
|
Type A (direct probe) |
Security
|
Security seals Serialised plastic security seals Tamper terminal cover Load disconnection on tamper detection No power tamper (optional) |
Standards |
IEC 62052-11 IEC 62053-21 IEC 62055-41 IEC 62056-21 IEC 60068-2-27 IEC 60068-2-6 SANS 1524-1 ISO 14001:2004 ISO 9001:2008 ISO 18001 |
Packaging
|
1 1.3kg 78mm: 360mm : 180mm Air: 255 Sea : 390 1,200mm : 1,000mm (2-way) Air: 344kg Sea: 519kg |
Code | Description |
---|---|
#000# |
Dispenser test (STSO) |
#001# |
Load switch test (STS1) |
#002# |
Display test (STS2) |
#003# |
Input test device (STS6) |
#004# |
Accumulated energy consumed - MTTD (STS3) |
#005# |
Key revision and key type (STS4) |
#006# |
Tariff index (STS5) |
#007# |
Maximum power limit (STS7) |
#008# |
Tamper status (STS8) |
#009# |
Available credit |
#010# |
Phase unbalance (STS11) |
#011# - #029# |
STS reserved |
Code | Description |
---|---|
#200# |
Value of last credit token entered |
#201# |
ID of last credit token entered |
#202# |
Value of 2nd last credit token entered |
#203# |
ID of 2nd last credit token entered |
#204# |
Value of 3rd last credit token entered |
#205# |
ID of 3nd last credit token entered |
#206# |
Value of 4th last credit token entered |
#207# |
ID of 4th last credit token entered |
#208# |
Value of 5th last credit token entered |
#209# |
ID of 5th last credit token entered |
#210# - #248# |
Not used: value of credit token entered (6th - 25th tokens) |
#211# - #249# |
Not used: value of credit token entered (6th - 25th tokens) |
#251# |
Most recent token (Class, subclass, 20 digits, value) |
#252# |
2nd most recent token (Class, subclass, 20 digits, value) |
#253# |
3rd most recent token (Class, subclass, 20 digits, value) |
#254# |
4th most recent token (Class, subclass, 20 digits, value) |
#255# |
5th most recent token (Class, subclass, 20 digits, value) |
#256# |
6th most recent token (Class, subclass, 20 digits, value) |
#257# |
7th most recent token (Class, subclass, 20 digits, value) |
#258# |
8th most recent token (Class, subclass, 20 digits, value) |
#259# |
9th most recent token (Class, subclass, 20 digits, value) |
#260# |
10th most recent token (Class, subclass, 20 digits, value) |
#261# - #270# |
Not used |
#271# |
Estimated average daily and 30 day consumption |
#272# |
Last hour, 24 hour and 30 day consumption |
#273# |
Number of supply interruptions |
#274# |
Number of tamper detections |
#275# |
Lost communications counter |
#276# |
Eeprom memory data dump |
#277# |
Active load restriction duration and value |
#278# - #299# |
Not used |
Code | Description |
---|---|
#050# |
Instantaneous power (STS9) |
#051# |
GPS coordinates |
#052# - #069# |
STS reserved |
#070# |
Power consumption per phase |
#071# |
Current consumption per phase |
#072# |
Average voltage per phase |
#073# |
Reason for last disconnect |
#074# |
Time remaining till zero credit |
#075# |
RF signal strenth |
#076# |
User total consumption to date |
#077# |
Total user credit entered |
#078# |
STS token result |
#079# |
Manual reconnect |
#080# |
UIU reset |
#081# |
Display UIU refresh interval |
#082# |
Meter tamper switch status |
#083# |
Not used |
#084# |
Last post paid / prepaid tenancy change MTTD register |
#085# |
Manual disconnect |
#086# |
Reactive power and power factor |
#087# |
Display consumption counter |
#088# |
Currently active load limit value |
#089# - #099# |
Not used |